Analysing electrical demand and supply (kW, kVAR, kVA, PF, V)

Reducing energy costs starts by understanding what’s driving your energy use and how efficient your electrical installation is. You may be familiar with monitoring your kWh consumption from electricity bills and from more granular dashboard reports, but it’s now time to get started with what’s really happening with your electrical loads (appliances, machines, etc).

 

The theory part

In AC circuit analysis, both voltage and current vary sinusoidally with time. The presence of reactive elements like inductors and capacitors directly impact the current wave by shifting it with respect to voltage wave (φ), see below.

 

 

Power is the rate at which energy is consumed by an electrical load or produced by a generator, and the value of instantaneous power is obtained by multiplying instantaneous voltage with instantaneous current.

Instantaneous power varies with time sinusoidally, so we generally look at the average power within a given time frame, for example the period of the sinusoidal wave. The average power is calculated as:

P = Vrms x Irms x cosφ (W)
Vrms = RMS Voltage = Vm/√2
Irms = RMS Current = Im/√2
Vm and Im the maximum values of the sinusoidal voltage and current
 

 

This average power formula is the basis to calculate the power consumed by the load over longer periods, for example your monthly electric energy bills are based on this power calculation. Note that the average power is also called ‘Real’, ‘True” or ‘Active’ power within the industry, and is measured in Watts (W). At Wattics we talk about Active Power.

 

In ideal inductors and capacitors, voltages are respectively 90° ahead and behind the phase of the current, meaning that ideal inductors and capacitors do not, on average, take active power from the circuit (cosφ=0). Current is instead used to charge a capacitor, or to create the magnetic field around a coil, as opposed to creating heat or lifting loads.

In real-world environments where resistors, inductors and capacitors are all combined within complex machines, the power that is wasted and not used to do work on the load is represented by the Reactive Power, calculated as:

Reactive Power = Vrms x Irms x sinφ (VAR)
Note that the Reactive Power is also called ‘Wattless’ power within the industry, and is measured in VAR (VoltAmpereReactive). At Wattics we talk about Reactive Power.

 

Apparent power represents the power that is supplied to the circuit (voltage multiplied by all the current that flows in it), and is measured in volt-amperes (VA). Apparent Power is calculated as follows:

Apparent power = Vrms x Irms (VA)
 

[Locker] The locker [id=3623] doesn't exist or the default lockers were deleted.

 

 

Wattics is a cloud-based Energy Management platform that can be presented to your customers as your own solution for energy monitoring, auditing, analysis and verification. Check out the capabilities of the Wattics dashboard to see if it is a fit for your project! Book a demo now by simply filling out the form below (this will only take 2 minutes of your time):

Your Name (required)

Your Email (required)

Your Phone Number (required)

Company Name (required)

Tell us about your energy analytics needs

Anthony Schoofs

Chief Technical Officer at Wattics
Anthony drives Wattics' innovation on energy efficiency for industrial and grid environments. Anthony is also behind WSNbuzz.com, a blog covering technology advances within the smart grid and IoT markets, and was listed in 2011 amongst the top 100 IoT thinkers. Anthony was recently awarded the Globe Sustainability Research Award for his contribution to advancing knowledge on sustainability.